( Manually typed words are colored purple in this demo.  Everything else came from the program itself. )
Mr. Arlos  Moore 
Global Enterprises 
123 Hopson Rd. 
Attn: Facilities Management 
Research Triangle Park  NC  27609 
Dear  Arlos
      Thank you for the opportunity to perform an inspection on your HVAC system.  The inspection is now complete, and we 
would like to take a moment to let you know our findings, and to make sure we have answered any questions you might 
have. 
     As per your request, we have included all graphics and reports in both IP and SI units, side by side, for the convenience of 
your international operations. 
    Since, in fact, you are a hypothetical customer and do not really exist, and the purpose of this sample report is to show 
everything HVACSuite can do, we have taken the liberty of including many more reports and graphics than you would 
normally want to see in any one report.
   On the following pages, you will see our detailed report.  We summarize it here as follows : 
     Our technician noted that the filters in the unit are dirty, and in need of changing.
  We would like to recommend the following : 
[ recommendations here ]
            Filter change 
            Clean condensor coil ( pressure wash )
   If you have any questions, comments, or suggestions on how we can serve you better in the future, please call us ! 
   
   We appreciate your business !  Thank you ! 
Sincerely,  
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
  The following reports and graphics show the air-side performance of your system, as measured : 
   
  
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
  The following report shows the refrigeration-side performance of your system, as measured : 
[ insert refer report here from Refrigeration Systems screen ] 
[ etc ]
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
  The following report shows the refrigeration-side performance of your system, as measured : 
[ insert refer report here from Refrigeration Systems screen ] 
[ etc ]
Refrigeration system report 
Refrigerant  R - 22 
Evaporator suction line temperature =      42.1 F  ( 5.6 C ) 
suction line pressure  =            60  PSI-G  ( 413.7 KPA-G  /  4.14  Bar-G ) 
suction line saturation temp =  33.9 F  (1.0 C ) 
suction line superheat =          8.2 F  (4.6 C ) 
Condensor suction line temperature =       47.6 F  ( 8.7 C ) 
suction line pressure  =            58  PSI-G  ( 399.9 KPA-G  /  4.00  Bar-G ) 
suction line saturation temp =  32.4 F  (0.2 C ) 
suction line superheat =          15.2 F  (8.5 C ) 
Piping         suction line superheat gain =  7.0 F  (3.9 C ) 
suction line pressure drop =    2 PSI  ( 0.14 KPA ) 
Evaporator liquid line temperature =        80 F  ( 26.7 C ) 
liquid line pressure  =               185  PSI-G  ( 1,275.5 KPA-G  /  12.76  Bar-G ) 
liquid line saturation temp =     96.1 F  (35.6 C ) 
liquid line subcooling =            16.1 F  (9.0 C ) 
Condensor liquid line temperature =          82 F  ( 27.8 C ) 
liquid line pressure  =               189  PSI-G  ( 1,303.1 KPA-G  /  13.03  Bar-G ) 
liquid line saturation temp =     97.6 F  (36.4 C ) 
liquid line subcooling =            15.6 F  (8.6 C ) 
Piping         liquid line subcooling gain =    0.5 F  (0.4 C ) 
liquid line pressure drop =      4 PSI  ( 0.27 KPA ) 
Condensor discharge temperature =          120 F  ( 48.9 C ) 
discharge line pressure  =       191  PSI-G  ( 1,316.9 KPA-G  /  13.17  Bar-G ) 
discharge saturation temp =     98.3 F  (36.8 C ) 
discharge superheat =            21.7 F  (12.1 C ) 
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
PsychroCalc report  -  z Demo - Comparison to PMTHERM V 1.23 System example 01  RA vs SA Deltas ( states 3 & 4 )
           Altitude 0 Feet  0.0 Meters
# 1 = Room point
Point Source =  Absolute
DB  75  F ( 23.9 C )      WB   62.6  F ( 17.0 C )      Dew   55.1  F ( 12.8 C )          RH %     50 
Moisture  64.93 Grains  ( 0.00928 Lb/Lb ) ( 9.256 G/KG )   HumRatio .00928   SpecHum .00919 
Flow 3,545  SCFM ( 6,023 M^3/h) 16,092.4  Lb/Hour moist air ( 7,299 KG/Hour) 
Enthalpy  28.184  BTU/lb ( 65.513  KJ/KG ) ( 15.647  Cal/G ) 
.035  Lb/BTU  ( .01526  KG/KJ ) ( .06391  G/Cal ) 
Specific Volume  13.676  Ft^3/lb ( .85376 M^3/KG) Density  .07312  Lb/ft^3  ( 1.17129 KG/M^3) 
BTU content 7,490  BTU/Min ( 2,196  Watts/Min) ( 7,902  KJ/Min)   ( 1,889  KCal/Min) 
449,385  BTU/Hr  ( 132  KW/Hr) ( 474,127  KJ/Hr)   ( 113,319  KCal/Hr) 
# 2 = OA point
Point Source =  Absolute
DB  95  F ( 35.0 C )      WB   75.0  F ( 23.9 C )      Dew   66.4  F ( 19.1 C )          RH %     39.3 
Moisture  97.61 Grains  ( 0.01394 Lb/Lb ) ( 13.915 G/KG )   HumRatio .01394   SpecHum .01375 
Flow 1,000  SCFM ( 1,699 M^3/h) 4,560.5  Lb/Hour moist air ( 2,069 KG/Hour) 
Enthalpy  38.231  BTU/lb ( 88.865  KJ/KG ) ( 21.225  Cal/G ) 
.026  Lb/BTU  ( .01125  KG/KJ ) ( .04711  G/Cal ) 
Specific Volume  14.294  Ft^3/lb ( .89232 M^3/KG) Density  .06996  Lb/ft^3  ( 1.12068 KG/M^3) 
BTU content 2,866  BTU/Min ( 840  Watts/Min) ( 3,024  KJ/Min)   ( 723  KCal/Min) 
171,951  BTU/Hr  ( 50  KW/Hr) ( 181,418  KJ/Hr)   ( 43,360  KCal/Hr) 
# 3 = Mix process - 1 & 2
Point Source =  Process - Mix /2/1/3
DB  79.4  F ( 26.3 C )      WB   65.6  F ( 18.7 C )      Dew   58.0  F ( 14.4 C )          RH %     47.9 
Moisture  72.12 Grains  ( 0.01030 Lb/Lb ) ( 10.281 G/KG )   HumRatio .01030   SpecHum .01020 
Flow 4,545  SCFM ( 7,722 M^3/h) 20,652.9  Lb/Hour moist air ( 9,368 KG/Hour) 
Enthalpy  30.387  BTU/lb ( 70.634  KJ/KG ) ( 16.871  Cal/G ) 
.033  Lb/BTU  ( .01416  KG/KJ ) ( .05927  G/Cal ) 
Specific Volume  13.811  Ft^3/lb ( .86220 M^3/KG) Density  .07241  Lb/ft^3  ( 1.15982 KG/M^3) 
BTU content 10,353  BTU/Min ( 3,036  Watts/Min) ( 10,923  KJ/Min)   ( 2,611  KCal/Min) 
621,187  BTU/Hr  ( 182  KW/Hr) ( 655,387  KJ/Hr)   ( 156,641  KCal/Hr) 
# 4 = SA = Process - Relative 3 to 4, constant None.   DB+/- -22.4, RH+/- 40.9, Grains+/-
Point Source =  Process - Relative / ABS /           3/4/None/-22.4///40.9//
DB  57  F ( 13.9 C )      WB   55.1  F ( 12.8 C )      Dew   53.7  F ( 12.1 C )          RH %     88.8 
Moisture  61.66 Grains  ( 0.00881 Lb/Lb ) ( 8.791 G/KG )   HumRatio .00881   SpecHum .00873 
Flow 4,545  SCFM ( 7,722 M^3/h) 20,622.4  Lb/Hour moist air ( 9,354 KG/Hour) 
Enthalpy  23.274  BTU/lb ( 54.098  KJ/KG ) ( 12.921  Cal/G ) 
.043  Lb/BTU  ( .01848  KG/KJ ) ( .07739  G/Cal ) 
Specific Volume  13.204  Ft^3/lb ( .82433 M^3/KG) Density  .07573  Lb/ft^3  ( 1.21311 KG/M^3) 
BTU content 7,929  BTU/Min ( 2,325  Watts/Min) ( 8,366  KJ/Min)   ( 2,000  KCal/Min) 
475,768  BTU/Hr  ( 140  KW/Hr) ( 501,962  KJ/Hr)   ( 119,972  KCal/Hr) 
________________________________________________________________________________________________ 
________________________________________________________________________________________________ 
**************************   Deltas reporting point, from 3 to 4  **************************
# Delta point name =  Delta from 3  to # 4
Paul J Milligan     2212 Wininger Dr.    Raleigh, NC    26703     (919) 662-3227     pjm@pobox.com
From  #  3  Mix process - 1 & 2
To     #  4  SA = Process - Relative 3 to 4, constant None.   DB+/- -22.4, RH+/- 40.9, Grains+/-
DB  -22.4  F ( -12.4 C )      WB   -10.5  F ( -5.8 C )      Dew   -4.3  F ( -2.4 C )      RH %     40.9 
Moisture  -10.46 Grains  ( -0.00149 Lb/Lb ) ( -1.490 G/KG )   HumRatio -.00149   SpecHum -.00147 
-30.5  Lbs/hr ( -13.8  KG/hr ) -3.7  Gal/hr ( -13.8  Liter/hr ) 
Flow 0  SCFM ( 0 M^3/h) -30.5  Lb/Hour moist air ( -14 KG/Hour) 
Enthalpy  -7.114  BTU/lb ( -16.535  KJ/KG ) ( -3.949  Cal/G ) 
.010  Lb/BTU  ( .00433  KG/KJ ) ( .01812  G/Cal ) 
Specific Volume  -.607  Ft^3/lb  ( -.03788 M^3/KG) Density  .00333  Lb/ft^3  ( .05329 KG/M^3) 
BTU content -2,424  BTU/Min ( -711  Watts/Min) ( -2,557  KJ/Min)   ( -611  KCal/Min) 
-145,419  BTU/Hr  ( -42.6  KW/Hr) ( -153,425  KJ/Hr)   ( -36,669  KCal/Hr) 
SHR 
Tons  Total        12.1    0.76 CFM/ton   375 
           Sensible  9.2  ( 110,133  BTUH )  ( 32.3  KW/H )  ( 116,196  KJ/H )  ( 27,772  KCal/H ) 
           Latent      2.9  ( 35,286  BTUH )  ( 10.3  KW/H )  ( 37,229  KJ/H )  ( 8,898  KCal/H ) 
  We gladly accept all major credit cards. 
           