7/26/2005 4:53:33 AM Page  1
    This demo simply runs each of the available calculations in the list, with some arbitrary input numbers. 
______________________ 
Air flow - get BTUH from CFM and T.D.
CFM = 1000 ,  T.D. = 19  ,  Calculated Sensible Heat BTUH = 20,394 
______________________ 
Air flow - get CFM from BTUH and T.D.
BTUH = 20394 ,  T.D. = 19  ,  Calculated CFM = 1,000 
______________________ 
Air flow - get T.D. from CFM and BTUH
 CFM input = 1000 , BTUH input = 20394, calculated TD = 19 
______________________ 
Fan laws - change RPM, get new Static, CFM, and BHP
Old RPM = 850 Old Static = 0.5 Old CFM = 1000 Old HP = 2 
New RPM = 1075 
New Static = 0.8 
New CFM = 1265 
New HP = 4.05 
______________________ 
Fan laws - get new Amps from new RPM and old actual Amps
Old RPM = 850 Old Amps = 1.6 
New RPM = 1075 New Amps = 3.24 
______________________ 
Loan summary calculation 
Input :  
Amount 10000 
Months 240 
Interest % / year 8.5 
Output :  
Monthly payment 86.78 
Yearly payment 1,041.39 
Total interest 10,827.76 
Total payments 20,827.76 
______________________ 
Loan schedule calculation 
Input :  
Amount 5000 
Months 24 
Interest % / year 8.5 
Start Month/Year 7/2005 
Output :  
Monthly payment 227.28 
Yearly payment 2,727.34 
Total interest 454.68 
Total payments 5,454.68 
Period  Interest    Principal Total Balance
001     07/2005         35.42 191.86 227.28 4,808.14 
002     08/2005         34.06 193.22 227.28 4,614.92 
003     09/2005         32.69 194.59 227.28 4,420.33 
004     10/2005         31.31 195.97 227.28 4,224.36 
005     11/2005         29.92 197.36 227.28 4,027.00 
006     12/2005         28.52 198.75 227.28 3,828.25 
Calendar year  191.92 1,171.75 1,363.67
Period Interest    Principal Total Balance
007     01/2006         27.12 200.16 227.28 3,628.09 
008     02/2006         25.70 201.58 227.28 3,426.51 
009     03/2006         24.27 203.01 227.28 3,223.50 
010     04/2006         22.83 204.45 227.28 3,019.06 
011     05/2006         21.38 205.89 227.28 2,813.16 
HVACSuite.com
7/26/2005 4:53:33 AM Page  2
012     06/2006         19.93 207.35 227.28 2,605.81 
013     07/2006         18.46 208.82 227.28 2,396.99 
014     08/2006         16.98 210.30 227.28 2,186.69 
015     09/2006         15.49 211.79 227.28 1,974.90 
016     10/2006         13.99 213.29 227.28 1,761.61 
017     11/2006         12.48 214.80 227.28 1,546.81 
018     12/2006         10.96 216.32 227.28 1,330.49 
Calendar year  229.58 2,497.76 2,727.34
Period Interest    Principal Total Balance
019     01/2007         9.42 217.85 227.28 1,112.64 
020     02/2007         7.88 219.40 227.28 893.24 
021     03/2007         6.33 220.95 227.28 672.29 
022     04/2007         4.76 222.52 227.28 449.77 
023     05/2007         3.19 224.09 227.28 225.68 
024     06/2007         1.60 225.68 227.28 .00 
Calendar year  33.18 1,330.49 1,363.67
______________________ 
Metal Ducts - get duct size options from CFM & FPM
CFM =  1000 , FPM = 850 Pvel = 0.045 
Round metal duct equivalent = 14.7
Surface / 10 ' = 38.5 sq ft FPM = 850   Pvel = 0.045    FL / 100 ' = 0.074 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      83.0   63.7   54.1   44.5   34.9 
Aluminum     21.9     17.4     13.7     10.9     8.6 
Rectangular metal duct equivalent ( equal friction ) = 13.4 " x 13.4 " aspect ratio = 1
Surface / 10 ' = 44.7 sq ft    FPM = 802   Pvel = 0.04 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      96.3   74.0   62.8   51.6   40.5 
Aluminum     25.4     20.2     15.9     12.7     10.0 
Equivalents for equal friction ( metal duct ) : 
2  "  x  199 " Aspect = 99.500 Surface / 10 ' = 335.0 sq ft    FPM = 362   Pvel = 0.008 
4  "  x  65 " Aspect = 16.250 Surface / 10 ' = 115.0 sq ft    FPM = 554   Pvel = 0.019 
6  "  x  35 " Aspect = 5.833 Surface / 10 ' = 68.3 sq ft    FPM = 686   Pvel = 0.029 
8  "  x  24 " Aspect = 3.000 Surface / 10 ' = 53.3 sq ft    FPM = 750   Pvel = 0.035 
10  "  x  18 " Aspect = 1.800 Surface / 10 ' = 46.7 sq ft    FPM = 800   Pvel = 0.04 
12  "  x  15 " Aspect = 1.250 Surface / 10 ' = 45.0 sq ft    FPM = 800   Pvel = 0.04 
14  "  x  13 " Aspect = 1.077 Surface / 10 ' = 45.0 sq ft    FPM = 791   Pvel = 0.039 
16  "  x  11 " Aspect = 1.455 Surface / 10 ' = 45.0 sq ft    FPM = 818   Pvel = 0.042 
18  "  x  10 " Aspect = 1.800 Surface / 10 ' = 46.7 sq ft    FPM = 800   Pvel = 0.04 
20  "  x  9 " Aspect = 2.222 Surface / 10 ' = 48.3 sq ft    FPM = 800   Pvel = 0.04 
______________________ 
Metal Ducts - get duct size options from CFM & Friction Loss / 100 ft
CFM   =  1000 FL/100   =  0.07 Length = 35 
Round metal duct equivalent = 14.8 " ( 37.6 cm )
Surface / 10 ' = 38.7 sq ft    FPM = 837   Pvel = 0.044    FL / 100 ' = 0.072   FL / 35 ' = 0.0252 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      83.5   64.2   54.5   44.8   35.1 
Aluminum     22.0     17.5     13.8     11.0     8.7 
Rectangular metal duct equivalent ( equal friction ) = 13.5 " x 13.5 " aspect ratio = 1
Surface / 10 ' = 45.0 sq ft    FPM = 790   Pvel = 0.039 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      97.0   74.5   63.3   52.0   40.8 
Aluminum     25.6     20.3     16.1     12.8     10.1 
Equivalents for equal friction ( metal duct ) : 
4  "  x  67 " Aspect = 16.750 Surface / 10 ' = 118.3 sq ft    FPM = 537   Pvel = 0.018 
6  "  x  36 " Aspect = 6.000 Surface / 10 ' = 70.0 sq ft    FPM = 667   Pvel = 0.028 
8  "  x  25 " Aspect = 3.125 Surface / 10 ' = 55.0 sq ft    FPM = 720   Pvel = 0.032 
10  "  x  19 " Aspect = 1.900 Surface / 10 ' = 48.3 sq ft    FPM = 758   Pvel = 0.036 
12  "  x  15 " Aspect = 1.250 Surface / 10 ' = 45.0 sq ft    FPM = 800   Pvel = 0.04 
HVACSuite.com
7/26/2005 4:53:33 AM Page  3
14  "  x  13 " Aspect = 1.077 Surface / 10 ' = 45.0 sq ft    FPM = 791   Pvel = 0.039 
16  "  x  12 " Aspect = 1.333 Surface / 10 ' = 46.7 sq ft    FPM = 750   Pvel = 0.035 
18  "  x  10 " Aspect = 1.800 Surface / 10 ' = 46.7 sq ft    FPM = 800   Pvel = 0.04 
20  "  x  10 " Aspect = 2.000 Surface / 10 ' = 50.0 sq ft    FPM = 720   Pvel = 0.032 
22  "  x  9 " Aspect = 2.444 Surface / 10 ' = 51.7 sq ft    FPM = 727   Pvel = 0.033 
______________________ 
Metal Ducts - get duct size options from CFM & Rectangular Dimensions
Side 1 " = 22 Side 2 " = 12 CFM = 1000 Length = 35 
Round metal duct equivalent = 17.6 " ( 44.7 cm )
Surface / 10 ' = 46.1 sq ft    FPM = 592   Pvel = 0.022    FL / 100 ' = 0.029   FL / 35 ' = 0.01015 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      99.3   76.3   64.8   53.3   41.7 
Aluminum     26.2     20.8     16.4     13.1     10.3 
Rectangular metal duct equivalent ( equal friction ) = 22 " x 12 " aspect ratio = 1.833
Surface / 10 ' = 56.7 sq ft    FPM = 545   Pvel = 0.019 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      122.2   93.8   79.7   65.5   51.3 
Aluminum     32.2     25.6     20.2     16.1     12.7 
Equivalents for equal friction ( metal duct ) : 
12  "  x  22 " Aspect = 1.833 Surface / 10 ' = 56.7 sq ft    FPM = 545   Pvel = 0.019 
14  "  x  18 " Aspect = 1.286 Surface / 10 ' = 53.3 sq ft    FPM = 571   Pvel = 0.02 
16  "  x  16 " Aspect = 1.000 Surface / 10 ' = 53.3 sq ft    FPM = 562   Pvel = 0.02 
18  "  x  14 " Aspect = 1.286 Surface / 10 ' = 53.3 sq ft    FPM = 571   Pvel = 0.02 
20  "  x  13 " Aspect = 1.538 Surface / 10 ' = 55.0 sq ft    FPM = 554   Pvel = 0.019 
22  "  x  12 " Aspect = 1.833 Surface / 10 ' = 56.7 sq ft    FPM = 545   Pvel = 0.019 
24  "  x  11 " Aspect = 2.182 Surface / 10 ' = 58.3 sq ft    FPM = 545   Pvel = 0.019 
26  "  x  10 " Aspect = 2.600 Surface / 10 ' = 60.0 sq ft    FPM = 554   Pvel = 0.019 
28  "  x  10 " Aspect = 2.800 Surface / 10 ' = 63.3 sq ft    FPM = 514   Pvel = 0.016 
30  "  x  9 " Aspect = 3.333 Surface / 10 ' = 65.0 sq ft    FPM = 533   Pvel = 0.018 
______________________ 
Metal Ducts - get duct size options from CFM & Round Diameter
Diam. inch  = 14 CFM = 800 Length = 65 
Round metal duct equivalent =   =  14 inches  CFM   =  800 Length   =  65 feet 
Surface / 10 ' = 36.7 sq ft    FPM = 748   Pvel = 0.035    FL / 100 ' = 0.062   FL / 65 ' = 0.0403 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      79.0   60.7   51.5   42.4   33.2 
Aluminum     20.9     16.6     13.1     10.4     8.2 
Rectangular metal duct equivalent ( equal friction ) = 12.7 " x 12.7 " aspect ratio = 1
Surface / 10 ' = 42.3 sq ft    FPM = 714   Pvel = 0.032 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      91.3   70.1   59.5   48.9   38.4 
Aluminum     24.1     19.1     15.1     12.0     9.5 
Equivalents for equal friction ( metal duct ) : 
2  "  x  174 " Aspect = 87.000 Surface / 10 ' = 293.3 sq ft    FPM = 331   Pvel = 0.007 
4  "  x  57 " Aspect = 14.250 Surface / 10 ' = 101.7 sq ft    FPM = 505   Pvel = 0.016 
6  "  x  31 " Aspect = 5.167 Surface / 10 ' = 61.7 sq ft    FPM = 619   Pvel = 0.024 
8  "  x  21 " Aspect = 2.625 Surface / 10 ' = 48.3 sq ft    FPM = 686   Pvel = 0.029 
10  "  x  16 " Aspect = 1.600 Surface / 10 ' = 43.3 sq ft    FPM = 720   Pvel = 0.032 
12  "  x  13 " Aspect = 1.083 Surface / 10 ' = 41.7 sq ft    FPM = 738   Pvel = 0.034 
14  "  x  12 " Aspect = 1.167 Surface / 10 ' = 43.3 sq ft    FPM = 686   Pvel = 0.029 
16  "  x  10 " Aspect = 1.600 Surface / 10 ' = 43.3 sq ft    FPM = 720   Pvel = 0.032 
18  "  x  9 " Aspect = 2.000 Surface / 10 ' = 45.0 sq ft    FPM = 711   Pvel = 0.032 
20  "  x  8 " Aspect = 2.500 Surface / 10 ' = 46.7 sq ft    FPM = 720   Pvel = 0.032 
______________________ 
Metal Ducts - Heat gain / loss in insulated metal ducts
Side 1 = 20" Side 2 = 30" Length = 25  ft CFM = 5000 
Added R-value = 6 Entering DB = 140 Outer (surrounding) DB = 40 
Surface / 10 ' = 83.3 sq ft Velocity = 1200 FPM Pvel = 0.09 
R value of the metal = 1.6 Total R value = 7.6 Net U value = 0.13158 
HVACSuite.com
7/26/2005 4:53:33 AM Page  4
BTUH gain / loss = -2,741  BTUH  DB gain / loss = -0.5 F Final supply air DB = 139.5 F 
Round metal duct equivalent = 26.6 "
Surface / 10 ' = 69.6 sq ft Velocity = 1296 FPM Pvel = 0.105 
FL / 100 ' = 0.082 " WG FL / 25 ' = 0.0205 
BTUH gain / loss = -2,291  BTUH  DB gain / loss = -0.4 F Final supply air DB = 139.6 F 
______________________ 
Metal Ducts - Rectangular to Round equivalent and options, equal friction
Side 1 " = 20 Side 2 " = 30 CFM = 5000 Length = 65 
Round metal duct equivalent = 26.6 " ( 67.6 cm )
Surface / 10 ' = 69.6 sq ft    FPM = 1296   Pvel = 0.105    FL / 100 ' = 0.082   FL / 65 ' = 0.0533 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      150.1   115.3   97.9   80.5   63.1 
Aluminum     39.6     31.5     24.9     19.8     15.6 
Rectangular metal duct equivalent ( equal friction ) = 20 " x 30 " aspect ratio = 1.5
Surface / 10 ' = 83.3 sq ft    FPM = 1200   Pvel = 0.09 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      179.7   138.0   117.2   96.3   75.5 
Aluminum     47.4     37.7     29.8     23.7     18.7 
Equivalents for equal friction ( metal duct ) : 
10  "  x  73 " Aspect = 7.300 Surface / 10 ' = 138.3 sq ft    FPM = 986   Pvel = 0.061 
12  "  x  56 " Aspect = 4.667 Surface / 10 ' = 113.3 sq ft    FPM = 1071   Pvel = 0.072 
14  "  x  46 " Aspect = 3.286 Surface / 10 ' = 100.0 sq ft    FPM = 1118   Pvel = 0.078 
16  "  x  39 " Aspect = 2.438 Surface / 10 ' = 91.7 sq ft    FPM = 1154   Pvel = 0.083 
18  "  x  34 " Aspect = 1.889 Surface / 10 ' = 86.7 sq ft    FPM = 1176   Pvel = 0.086 
20  "  x  30 " Aspect = 1.500 Surface / 10 ' = 83.3 sq ft    FPM = 1200   Pvel = 0.09 
22  "  x  27 " Aspect = 1.227 Surface / 10 ' = 81.7 sq ft    FPM = 1212   Pvel = 0.092 
24  "  x  25 " Aspect = 1.042 Surface / 10 ' = 81.7 sq ft    FPM = 1200   Pvel = 0.09 
26  "  x  23 " Aspect = 1.130 Surface / 10 ' = 81.7 sq ft    FPM = 1204   Pvel = 0.09 
28  "  x  21 " Aspect = 1.333 Surface / 10 ' = 81.7 sq ft    FPM = 1224   Pvel = 0.093 
______________________ 
Metal Ducts - Round to Rectangular equivalent and options, equal friction
Diam. inch  = 12 CFM = 800 Length = 75 
Round metal duct equivalent =   =  12 inches  CFM   =  800 Length   =  75 feet 
Surface / 10 ' = 31.4 sq ft    FPM = 1019   Pvel = 0.065    FL / 100 ' = 0.138   FL / 75 ' = 0.1035 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      67.7   52.0   44.2   36.3   28.5 
Aluminum     17.9     14.2     11.2     8.9     7.0 
Rectangular metal duct equivalent ( equal friction ) = 10.9 " x 10.9 " aspect ratio = 1
Surface / 10 ' = 36.3 sq ft    FPM = 970   Pvel = 0.059 
Lbs / 10 ' 18 ga. 20 ga. 22 ga. 24 ga. 26 ga. 
Gal. steel      78.3   60.2   51.1   42.0   32.9 
Aluminum     20.7     16.4     13.0     10.3     8.1 
Equivalents for equal friction ( metal duct ) : 
2  "  x  116 " Aspect = 58.000 Surface / 10 ' = 196.7 sq ft    FPM = 497   Pvel = 0.015 
4  "  x  38 " Aspect = 9.500 Surface / 10 ' = 70.0 sq ft    FPM = 758   Pvel = 0.036 
6  "  x  22 " Aspect = 3.667 Surface / 10 ' = 46.7 sq ft    FPM = 873   Pvel = 0.048 
8  "  x  15 " Aspect = 1.875 Surface / 10 ' = 38.3 sq ft    FPM = 960   Pvel = 0.057 
10  "  x  12 " Aspect = 1.200 Surface / 10 ' = 36.7 sq ft    FPM = 960   Pvel = 0.057 
12  "  x  10 " Aspect = 1.200 Surface / 10 ' = 36.7 sq ft    FPM = 960   Pvel = 0.057 
14  "  x  9 " Aspect = 1.556 Surface / 10 ' = 38.3 sq ft    FPM = 914   Pvel = 0.052 
16  "  x  8 " Aspect = 2.000 Surface / 10 ' = 40.0 sq ft    FPM = 900   Pvel = 0.05 
18  "  x  7 " Aspect = 2.571 Surface / 10 ' = 41.7 sq ft    FPM = 914   Pvel = 0.052 
20  "  x  6 " Aspect = 3.333 Surface / 10 ' = 43.3 sq ft    FPM = 960   Pvel = 0.057 
______________________ 
Pulleys - get belt size from pulley sizes and shaft distance
Motor pulley = 8" Blower pulley = 14"    Shafts C-2-C = 20" Belt size = 75 " 
Note - always set the motor mounting base to mid-point in the adjusting slots before measuring  
HVACSuite.com
7/26/2005 4:53:33 AM Page  5
C2C shaft distance so you have maximum adjustability for the new belt. 
______________________ 
Pulleys - get blower RPM, CFM, BHP, Amps from pulley size changes and motor RPM
Old RPM = 850 Old Motor pulley  = 8" Old Blower Pulley  = 14" Old BHP = 5 
Old CFM  = 1200 Old Blower RPM  = 486 Old Amps = 6 
New RPM = 1075 New Motor pulley  = 10" New Blower Pulley  = 12" New BHP = 31.33 
New CFM  = 2212 New Blower RPM  = 896 New Amps = 37.6 
Shafts C-2-C = 24" Belt size = 83 " 
Note - always set the motor mounting base to mid-point in the adjusting slots before measuring  
C2C shaft distance so you have maximum adjustability for the new belt. 
______________________ 
Pump laws - Change impeller diameter, get new FOH, BHP, RPM, GPM
Old Impeller diameter input = 6 
Feet of head input = 12 
BHP input = 5 
RPM input = 850 
GPM input = 1000 
New Impeller diameter input = 8 
New Feet of Head = 21.3 
New BHP = 11.85 
New GPM = 1,333.3 
______________________ 
Pump laws - Change RPM, get new FOH, BHP, RPM, GPM
Old RPM input = 850 
Impeller diameter input = 6 
Feet of head input = 12 
BHP input = 5 
GPM input = 1000 
New RPM input = 1075 
New Feet of Head = 19.2 
New BHP = 10.11 
New GPM = 1,264.7 
HVACSuite.com