Refrigeration system report 
Refrigerant  R - 22 
Evaporator suction line temperature =      42.1 F  ( 5.6 C ) 
suction line pressure  =            60  PSI-G  ( 413.7 KPA-G  /  4.14  Bar-G ) 
suction line saturation temp =  33.9 F  (1.0 C ) 
suction line superheat =          8.2 F  (4.6 C ) 
Condensor suction line temperature =       47.6 F  ( 8.7 C ) 
suction line pressure  =            58  PSI-G  ( 399.9 KPA-G  /  4.00  Bar-G ) 
suction line saturation temp =  32.4 F  (0.2 C ) 
suction line superheat =          15.2 F  (8.5 C ) 
Piping         suction line superheat gain =  7.0 F  (3.9 C ) 
suction line pressure drop =    2 PSI  ( 0.14 KPA ) 
Evaporator liquid line temperature =        80 F  ( 26.7 C ) 
liquid line pressure  =               185  PSI-G  ( 1275.5 KPA-G  /  12.76  Bar-G ) 
liquid line saturation temp =     96.1 F  (35.6 C ) 
liquid line subcooling =            16.1 F  (9.0 C ) 
Condensor liquid line temperature =          82 F  ( 27.8 C ) 
liquid line pressure  =               189  PSI-G  ( 1303.1 KPA-G  /  13.03  Bar-G ) 
liquid line saturation temp =     97.6 F  (36.4 C ) 
liquid line subcooling =            15.6 F  (8.6 C ) 
Piping         liquid line subcooling gain =    0.5 F  (0.4 C ) 
liquid line pressure drop =      4 PSI  ( 0.27 KPA ) 
Condensor discharge temperature =          120 F  ( 48.9 C ) 
discharge line pressure  =       191  PSI-G  ( 1316.9 KPA-G  /  13.17  Bar-G ) 
discharge saturation temp =     98.3 F  (36.8 C ) 
discharge superheat =            21.7 F  (12.1 C ) 
AHU Air R/A = 74 F ( 23.3  C )  RH = 50 S/A = 52 F ( 11.1  C )  RH = 95 Delta =  -22 F  (-12.2 C ) 
CFM = 1200 
Condensor Air Ambient air = 92 F ( 33.3  C )  Discharge air = 130 F ( 54.4  C )  Delta =  38 F  (21.1 C ) 
AHU KWH 0.5  ( 0.72  HP ) Condensor KWH  = 2.2  ( 2.98  HP ) 
Total KWH 2.8  ( 3.71  HP ) Compressor KWH  = 1.8  KWH  ( 2.47  HP ) 
Actual BTUH Capacity RA -> SA 35,619 Total  ( 2.97 Tons ) EER BTU/W   =  12.9 KWH / Ton  = .9 
Program comment  :   Condensor  air Delta is >30 F .  May indicate a dirty coil, bad fan, or recirculating condensor air.  
Program comment  :   Evaporator  LL Sub-cooling is >15.  May indicate restriction, overcharge, bad/wrong metering device, or non-
condensibles. 
Program comment  :   Condensor  Sub-cooling is > 15.  May indicate restriction, overcharge, bad/wrong metering device, or non-
condensibles. 